Key takeaways
- Free area ratio is 1 minus blade depth times sine of the blade angle divided by pitch, so a 40 mm blade at 45° on a 50 mm pitch gives 43%.
- Size the louvre at 4.5–5 m/s through the free area: a 3.0 m³/s genset radiator needs 0.67 m² of free area, which is 1.55 m² of louvre at 43%.
- Below 45° of blade angle rain carries through above 2 m/s, so outdoor canopies use 45–60° with a gutter behind the blade row.
- Support blades at 1,200 mm maximum: a 1.5 mm blade 40 mm deep deflects about 0.3 mm at 1,200 mm under 0.5 kPa and 1.6 mm at 1,800 mm.
- Bird mesh at 12.5 mm costs 15–20% of the free area, so size the opening for the mesh, not for the bare louvre.
Louvre design is an airflow problem and a stiffness problem in the same panel. Get the free area wrong and the genset overheats on the hottest day of the year; get the blade angle wrong and it rains inside the canopy; get the blade span wrong and the blades flap, take a permanent set and close the opening they were meant to provide. All three are decided on the drawing, before the tool is cut.
The arithmetic is short. Free area is the clear opening divided by the face area, and for a blade of depth d at angle theta on pitch p it works out at 1 minus d times sine theta divided by p. A 40 mm blade at 45° on a 50 mm pitch gives 43%. That single number then sets the panel size once you know the airflow.
What follows is the sizing route for a canopy or enclosure louvre, the rain and stiffness limits that come with it, and the note that has to be on the drawing so the panel is formed to the right angle rather than to whatever the tool happens to be set at.
Louvre design: how much free area does a panel give?
Free area is the projected clear opening through the blade row, not the area of the hole cut in the panel. A louvre cut into a 1,200 mm × 800 mm aperture and filled with 45° blades does not pass air through 0.96 m².
The geometric model is enough for sizing. Take blade depth d measured along the blade, pitch p measured vertically between blade leading edges, and blade angle theta measured from horizontal:
free area ratio = 1 − (d × sin θ) ÷ p
At d equal to 40 mm, p equal to 50 mm and theta equal to 45°, the ratio is 1 minus 28.3 divided by 50, which is 0.434. At 30° the same blade and pitch give 0.60, and at 60° they give 0.31.
Three practical corrections apply to that figure. Blade thickness eats a little of the opening. The frame and any mullion eat the perimeter. And any mesh behind the louvre costs 15–20% of what is left. A louvre quoted at 43% free area with 12.5 mm bird mesh behind it behaves like 35%, and a canopy sized on the bare figure will run short of air.
Louvre limits for canopy and enclosure work
| Parameter | Typical value | Ganesh limit or note |
|---|---|---|
| Blade angle from horizontal | 30–60° | 45° for outdoor rain rejection; 30° only under a roof |
| Blade depth to pitch ratio | 0.7–1.0 | Below 0.7 the blade row stops being a rain screen |
| Free area at 45°, d/p 0.8 | 40–45% | Use 43% for sizing; confirm on the first article |
| Free area at 30°, d/p 0.8 | 55–60% | Higher flow, rain carry-over above 2 m/s |
| Face velocity through free area | 4.5–5.0 m/s | 3.0 m/s where rain or snow is possible |
| Pressure drop at 5 m/s | 30–40 Pa | ζ about 2.5; recalculate at the actual flow |
| Blade thickness | 1.2–2.0 mm CRCA | 1.5 mm for a 40 mm blade, 1.2 mm for 25 mm |
| Blade span between supports | 900–1,200 mm | 1,200 mm maximum; add a mullion above that |
| Blade deflection at 0.5 kPa | 0.3 mm at 1,200 mm span | 1.6 mm at 1,800 mm, which takes a set |
| Perimeter flange | 15 mm minimum | 10 mm buckles when the blade row is formed |
| Bird mesh | 12.5 mm aperture | Costs 15–20% of free area; size the opening for it |
| Louvre-to-wall standoff | 50 mm minimum | Closer and the wall short-circuits the discharge |
Sizing the louvre from the airflow
Start with the volumetric flow the radiator fan moves, not with the engine rating. A 250 kVA genset with a pusher fan typically moves about 3.0 m³/s through the radiator core at rated speed, and the canopy has to pass that plus the combustion air and a margin for a dirty core.
At 4.5 m/s through the free area, 3.0 m³/s needs 0.67 m² of free area. At 43% free area that is 1.55 m² of louvre face. A 1,200 mm × 1,300 mm opening is 1.56 m², so a panel roughly 1.3 m wide and 1.4 m tall carries the duty with the frame included.
Now check what the same louvre does at the other end of the year. At 2 m/s the pressure drop falls to about 6 Pa, so the fan is not working against the louvre in winter. At 6 m/s the drop rises to about 54 Pa and the fan curve moves to the left, which costs airflow exactly when the ambient is highest. That is why the velocity limit is a design limit and not a rule of thumb: the louvre's pressure drop is proportional to velocity squared, so a canopy sized at 6 m/s loses airflow twice as fast as one sized at 4.5 m/s when the core starts to block.
The same sum on a 100 kVA set at 1.4 m³/s gives 0.31 m² of free area and a 0.72 m² louvre, which is a panel about 900 mm × 800 mm.
Blade angle, rain and recirculation
Blade angle does two jobs. It sets the free area and it decides whether rain that hits the panel comes out the back.
At 45° with the air moving at 3 m/s, droplets hit the blade, run down the face and leave at the bottom of the blade row. At 30° the blade is closer to horizontal, the air turns less, and above about 2 m/s the droplets are carried off the blade tips and into the canopy. The symptom is not a puddle. It is a wet air filter, a corroded radiator fin and a complaint about the set "using water".
Three details make a 45° louvre behave:
- A gutter behind the bottom blade, formed into the panel with a 10 mm return and a drain slot, so water that reaches the back of the blade row leaves the panel instead of running down the inside face.
- A 50 mm standoff from the wall, so the discharge does not short-circuit back into the intake louvre on the same face. Recirculation raises the intake air temperature by 5–8 °C on a tight installation, which is more than the louvre saves.
- Blades pointing down and out, never up. An upward blade holds water in the fold and the fold rusts from the inside.
For a coastal or dusty site the angle goes to 60° and the velocity drops to 2.5 m/s. The louvre gets bigger, and the alternative is a weather hood with a separate demister, which is a different panel and a different tool.
Blade stiffness and where the mullion goes
A louvre blade is a narrow strip of 1.2–1.5 mm sheet spanning between the frame and any mullion. Its stiffness in the wind direction comes from the blade depth, and its deflection goes with the fourth power of the span, which is why the span limit is unforgiving.
Take a 40 mm deep blade in 1.5 mm CRCA. Treating it as a plate strip, the second moment of area is 1.5 × 40³ ÷ 12, or 8,000 mm⁴. Under 0.5 kPa of wind load, which is a 90 km/h gust, the deflection at mid-span works out at about 0.10 mm on a 900 mm span, 0.32 mm at 1,200 mm and 1.63 mm at 1,800 mm.
The first two are invisible. The third is not: 1.6 mm of set on a blade that started with a 20 mm clear gap closes 8% of the opening permanently, and the blade no longer points at 45°. Adding a mullion at 1,200 mm costs one extra laser-cut slot and a 20 mm wide strip; going to 2 mm blade thickness raises the stiffness by 2.4× and the weight by 33%, and it still deflects 0.69 mm at 1,800 mm.
The mullion itself has to be designed. A 20 mm × 1.5 mm flat strip welded between two blade rows will bow when it is welded at both ends. Form it as a channel, or let it into a slot in the blade and weld only the ends.
Louvre, airflow and noise
On an acoustic canopy the louvre is the weakest path in the enclosure. A plain opening at 43% free area gives back 8–12 dB(A) of the attenuation the panels provide, because sound leaves through the same clear area the air uses.
Recovering that needs a splitter behind the louvre, and a splitter costs free area. A 100 mm deep splitter bank at 50% blockage adds about 40 Pa at 4.5 m/s and takes the free area down to roughly 22%, so the louvre panel doubles in size. That trade has to be made at the concept stage; a canopy designed at 43% free area cannot be fixed with a splitter after the tooling is cut.
Measurement is the other half. ISO 8528-10 sets out how airborne noise from a generating set is measured over an enveloping surface, and a canopy claim made without that method is not comparable with one that uses it. We do not run acoustic testing, so the sound figure has to come from the acoustic design and be verified by the test house.
What Ganesh runs
Pressed louvre panels are formed in a press tool built in our own tool room and run on the press line, which has 20–300 T mechanical presses and 250 T of punching capacity for wide panels. The aperture and the panel outline are cut on the 12 kW fibre laser on the 40 ft × 16 ft bed, so a 1,300 mm louvre panel and its mounting holes come off one nest.
Blade cassettes and louvre frames are formed on the 200 T, 5-axis brake with the 4,450 mm bed and welded at the manual stations or on the three CLOOS cells. Coating is seven-tank pretreatment, then powder in the 18 ft × 14 ft booth with a 60–80 µm target, which matters on a louvre because powder builds on the blade edge and closes the clear gap by about 0.14 mm per face.
We do not run airflow or acoustic testing. The free area is calculated and then confirmed by measuring the formed blade pitch and angle on the first article, and the pressure drop figure is a calculated value for the customer's fan curve to be checked against.
What to put on the drawing
- Required free area in m², not just the aperture size, and the flow it was calculated from.
- Blade angle from horizontal, with a tolerance of ±2° and the direction (down and out).
- Blade pitch and depth, or the free area ratio the tool has to achieve.
- Mullion positions, so the blade span stays at or under 1,200 mm.
- Mesh specification and whether it is included in the free area figure.
- Gutter and drain at the bottom blade, with the drain slot size.
- Standoff from the mating wall or panel, and whether a weather hood is required.
The genset canopy louvre design guide takes the same numbers into a full canopy layout, and the laser cutting guide for holes and slots covers the aperture cut quality that decides whether the blade row sits square in the frame.
When a louvre is the wrong answer
A louvre fails when the air has to be cleaned, when the site is exposed to driven rain or sand, and when the noise limit is tight. In each case the louvre is doing a job it was never designed for.
For sand and dust, a louvre is a separator only by accident. The blade row will stop coarse debris and pass everything under about 200 µm, and the filter behind it blocks twice as fast. A vane separator or an inertial pre-cleaner belongs upstream, and the louvre becomes a weather guard rather than a filter.
For driven rain at a coastal site, a 45° louvre at 5 m/s passes water. The answer is a weather hood with a baffle, or a demister, and both are deeper than the 100 mm a louvre needs. Designing a 60° louvre and calling it weatherproof is a common mistake that shows up as a wet floor under the set.
For tight noise limits, a louvre with a splitter may not fit the free area the engine needs. At that point the canopy moves to a remote radiator, a ducted discharge, or a larger enclosure with a dedicated attenuator, and the louvre panel becomes a small ventilation opening rather than the main air path.
Send the airflow, the ambient condition and the panel envelope through the RFQ route. The sheet metal stamping capability covers the press tools behind a pressed louvre, the genset parts range covers the canopy family, and the design and CAD hub collects the rest of the panel rules.
Frequently asked questions
How do I calculate the free area of a louvre?
Divide the clear opening by the total face. For a blade of depth d at angle theta on pitch p, the free area ratio is 1 minus d times sine theta divided by p. A 40 mm blade at 45° on a 50 mm pitch gives 43%.
What blade angle stops rain entering a genset canopy?
Forty-five degrees or steeper, with the air velocity through the free area under 3 m/s. At 30° and 5 m/s the blades throw water off the tips and the droplets carry into the radiator, which shows up as a wet filter rather than as a water leak.
How much does a louvre reduce genset noise attenuation?
A plain louvre opening gives back 8–12 dB(A) of the attenuation the canopy was designed for, depending on free area. A splitter or baffle behind the louvre recovers part of that, at the cost of free area and pressure drop.
What is the maximum unsupported blade span?
About 1,200 mm for a 1.5 mm blade 40 mm deep. At 1,800 mm the same blade deflects roughly 1.6 mm under 0.5 kPa of wind load and takes a permanent set. Add a mullion rather than a thicker blade.
Should louvres be pressed into the panel or bolted on as cassettes?
Press them into the panel when the blade angle is fixed and the panel is under about 1.5 m wide. Use a cassette when the angle has to be adjusted on site, when the blades need replacing, or when the panel is too large for a single press tool.
Sources and further reading
- ISO 8528-10 — Reciprocating internal combustion engine driven generating sets: measurement of airborne noise by the enveloping surface method · reviewed 3 Nov 2026
- ISO 5801 — Industrial fans: performance testing using standardized airways, including pressure and flow measurement · reviewed 3 Nov 2026
- ISO 2768-1 — General tolerances for linear and angular dimensions without individual tolerance indications · reviewed 3 Nov 2026