Key takeaways
- Size the louvres from heat rejection, not from appearance: a 250 kVA set rejects about 110–130 kW to cooling air, which is 6.5–7.5 m³/s at a 15 K rise through the canopy.
- The mass law gives 2 mm steel about 19 dB at 125 Hz and 31 dB at 500 Hz, but a canopy delivers 20–25 dB(A) overall because louvres, door seals and cable entries are the weak paths.
- Build the skin in 1.6–2.0 mm CRCA on a 2 mm formed frame, keep inside bend radius at 1t and hold the frame diagonal within ±1.5 mm before coating.
- Specify 70–90 µm of polyester powder over zinc phosphate for an ISO 12944-2 C3 site, and treat the base frame and the sill as C4.
- The 75 dB(A) at 1 m limit in Indian DG set rules is the number the acoustic target starts from, and a bare 250 kVA set runs 95–105 dB(A).
A DG set canopy is sold as a box and specified as two numbers: the airflow that keeps the set at its rated output on a 45 °C afternoon, and the sound pressure at 1 m that keeps the installation inside its permitted limit. Get either wrong and the canopy becomes the reason the site fails, not the thing that makes the set acceptable. The steelwork is the easy part; the design work is the opening area and the leak paths.
The mismatch shows up in the same way every time. A canopy sized around the set with 25% of its side covered in louvre looks generous, runs 8–10 °C above ambient inside, and derates a 250 kVA set by 10–15 kVA on the hottest day. The fix is not a bigger fan. It is louvre free area calculated from heat rejection, and a duct path that does not let the hot outlet air find the cold inlet.
This covers the four functions a canopy has to serve, the airflow arithmetic, the attenuation the panels actually deliver, the material and finish choices that survive an Indian site, and the cut, form, weld and coat route that turns 1.6 mm CRCA into a canopy that closes.
What does a DG set canopy have to do?
Four jobs, in order of how often they are done badly: pass cooling air, attenuate noise, keep weather out, and allow maintenance access.
Cooling comes first because it is the only one that changes the set's output. A diesel engine rejects roughly a quarter of its fuel energy through the radiator, and the alternator adds a few percent more. That heat leaves with the cooling air, and the air has to enter the canopy, cross the radiator and leave without mixing back into the inlet. A canopy that gets this right is a duct. A canopy that gets it wrong is a box with a hot corner.
Noise is second because it is regulated. Indian rules for diesel generator sets set a limit of 75 dB(A) at 1 m, and a bare 250 kVA set measures 95–105 dB(A) at that distance. The canopy therefore has to remove 20–30 dB(A), and it has to do so across the octave bands where the engine puts its energy, which is 63–500 Hz. That is the hard part, because low frequency sound is what thin steel panels pass most easily.
Weather and access come next, and they shape the details: door seals, louvre blades angled down, a roof that drains, a sill that sits above a plinth, hinges that do not sag after the two hundredth opening.
Sizing the airflow: the arithmetic behind the louvres
Start with the heat that has to leave. For a 250 kVA set running at 0.8 power factor, the engine burns fuel at roughly 500–540 kW to produce 200 kWe, and about 110–130 kW of that leaves through the radiator and the block surface into the canopy air.
Volume flow follows from the permitted temperature rise:
Q = P ÷ (ρ × cp × ΔT)
With P = 120 kW, air density at 40 °C of 1.13 kg/m³, cp of 1.005 kJ/kg·K and a 15 K rise, Q is 7.0 m³/s. A 20 K rise drops it to 5.3 m³/s, but it also means the air leaving the canopy is 20 K above ambient, and the radiator is being fed air that is already warm at the top of the enclosure.
Free area is next. At a face velocity of 3 m/s, 7.0 m³/s needs 2.33 m² of open area. A fixed 45° louvre with 55–65% free area therefore needs 3.6–4.2 m² of aperture, and that is for the outlet alone; the inlet needs the same area again, ideally on the opposite end and low down.
Three rules keep that geometry honest:
- Inlet low, outlet high, opposite ends. Hot air rises, and a high outlet at the radiator end pulls the flow across the set rather than letting it short-circuit over the top.
- Keep 1 m clear outside every louvre. A canopy pushed against a wall has an effective louvre area of whatever gap is left, and the set behaves as if the louvre were half the size.
- Do not count the door as inlet area. A door with a 5 mm gap around it leaks noise and dust, not the volume of air the arithmetic needs.
The same calculation is worth running at the site's altitude and ambient. A canopy designed at sea level and 40 °C loses about 3% of its air mass flow per 300 m of altitude, and the set's own derating curve does the rest.
Attenuation: what the panels give and what the leaks take away
Sound transmission through a single-leaf panel follows the mass law closely enough for design purposes:
TL ≈ 20 log₁₀(m × f) − 47 dB
where m is surface mass in kg/m² and f is frequency in Hz. For 2 mm steel at 15.7 kg/m², that gives about 19 dB at 125 Hz, 25 dB at 250 Hz, 31 dB at 500 Hz and 37 dB at 1 kHz. Doubling the mass adds 6 dB across the range; doubling the frequency also adds 6 dB.
Two conclusions follow. First, the low-frequency end is where a steel canopy is weakest, and that is exactly where a diesel engine is loudest. Second, adding mass to the panels has a predictable return, which is why 2 mm skin is common on larger canopies and 1.6 mm is enough on small ones.
The panel calculation is not the canopy specification, though. The overall attenuation is set by the weakest path, and the weak paths are the louvres, the door seals, the cable entry and the exhaust penetration. A fixed louvre gives 5–8 dB. An acoustic louvre with splitters gives 15–20 dB and costs 30–40% of its free area to do it, which puts the airflow calculation and the acoustic calculation in direct conflict. That conflict is the design.
| Element | Typical specification | Ganesh limit or note |
|---|---|---|
| Skin panel | 1.6–2.0 mm CRCA | Laser cut on a 12 kW machine with a 40 ft × 16 ft bed; a 4,000 mm side is one piece |
| Frame | 2.0 mm formed channel or 50 × 50 × 2 mm tube | Pressed and formed in house; fixtures built in the tool room |
| Louvre blade | 1.2 mm fixed, 45° | 55–65% free area; acoustic splitters cut free area by 30–40% |
| Panel length | Up to 4,000 mm | 200 T, 5-axis brake with a 4,450 mm bed; no join on a standard canopy side |
| Inside bend radius | 1t minimum | 1.6 mm on 1.6 mm skin; 2.0 mm avoids a sharp outer corner on a visible panel |
| Door | 1.5 mm skin, 20 mm return, 3 hinges | 700 × 1,400 mm typical; seal compressed 30–40% when latched |
| Frame squareness | ±1.5 mm on the diagonal | Checked in the fixture before welding out, not after coating |
| Skin mass | 12.6 kg/m² at 1.6 mm | 15.7 kg/m² at 2.0 mm; a 25 m² canopy is 315–390 kg of skin alone |
| Coating | 70–90 µm polyester powder | Seven-tank pretreatment; C3 site to ISO 12944-2, C4 for the sill and base frame |
| Acoustic target | 75 dB(A) at 1 m | Measured to ISO 8528-10 by the set OEM or a test house, not by the fabricator |
| Base frame | 100 × 50 × 5 mm channel | Welded with the canopy so mount holes and lifting points share one datum |
Materials: CRCA, galvanised or aluminium
CRCA is the default skin. It takes a bend, welds without porosity and holds powder over a zinc phosphate conversion. At 1.6 mm it is stiff enough for a 1,200 mm panel span without a stiffener, and at 2.0 mm it is quiet enough that a door closing does not sound like a drum.
Hot-dip galvanised sheet is cheaper to protect and worse to weld. The zinc burns back 5–10 mm from every weld, the weld itself needs a zinc-rich repair, and the repaired patch is the first place the coating fails. If the canopy is galvanised, it should be a bolted design with folded joints rather than a welded one. If it is welded, CRCA plus powder is the cleaner route.
Aluminium saves about two thirds of the skin mass and suits a canopy that has to be lifted onto a roof. It also has a third of the stiffness of steel, so the same panel needs a deeper return or a stiffener, and it needs isolation from a steel frame to stop galvanic corrosion at every fixing. We cut and form aluminium, but the finish is a different conversation: an aluminium canopy usually wants a mill finish or a paint system specified for aluminium, not the steel pretreatment sequence.
Stainless is for coastal and chemical sites and for canopies that will be washed down. It costs three to four times the CRCA panel and it work-hardens, so the bend radii go up and the laser cut edges need protection. It is the right answer for a handful of installations, not for a standard genset.
Framing is 2 mm formed channel or 50 × 50 × 2 mm tube, welded into a box with gussets at the corners. The frame carries the doors, the louvres and the lifting points, and it is the part that has to stay square through welding.
Coating a canopy for the site it will live in
A canopy is a large, thin, welded steel box with edges, weld toes and a sill that sits in water. That makes it a corrosion specification rather than a colour choice.
ISO 12944-2 classifies the environment from C1 to CX, and the category decides the system. A canopy in a covered plant room is C3: seven-tank pretreatment with a zinc phosphate conversion, then 70–90 µm of polyester powder. A canopy outdoors at a coastal site is C4 or C5: the same pretreatment, a zinc-rich primer on the welds and edges, and a heavier build. The base frame and the sill are C4 even when the panels are C3, because they sit in standing water and splash.
Three details matter more than the film thickness:
- Edge coverage. Powder thins over a laser-cut or sheared edge. A 70 µm face is often 40 µm at the edge, and that is where rust starts.
- Weld toes. A weld that has not been wire-brushed and blasted carries scale and spatter under the powder, and the film lifts there first.
- Masked faces. Door hinge faces, earth points and lifting eyes need bare metal or a masked thread, or the door will not align and the earth will not bond.
In-house checks are dry film thickness with a gauge and adhesion by cross-hatch, on the first part of each batch and on a sample door. A canopy that passes both still needs a visual check of every edge, because a missed edge is a warranty claim in eighteen months.
Doors, seals and the access that decides the noise figure
A canopy door is a 1 m² panel that has to seal against a fixed frame, swing on two or three hinges and survive being opened for every oil change. It is also the largest single leak path on the enclosure.
A 700 × 1,400 mm door in 1.5 mm CRCA weighs about 11.5 kg with its returns. On two hinges that is 5.8 kg per hinge plus the moment of a 700 mm lever, which is why three hinges and a 20 mm return around the perimeter are the minimum for a door of that size. A door that sags 2 mm at the latch corner compresses the seal unevenly: one corner seals, the other leaks a 2 mm gap along 300 mm, and that gap passes more high-frequency noise than the wall beside it blocks.
The seal is a hollow EPDM bulb, compressed 30–40% when latched. Compression below 25% leaves a path; above 50% the door is hard to close and the latch pulls the frame out of square over a few hundred cycles. Specify the seal by bulb diameter and compression, not by colour.
Latching is the other half. Two quarter-turn latches on a 1,400 mm door hold the middle, but the corners still lift unless the door has a return that seats against a stop. A cam latch with a 6 mm engagement and a nylon striker is enough for a canopy that is opened monthly; a lift-off hinge and a full-length piano hinge belong on a door that is opened weekly.
For access, the door has to clear the parts behind it: the oil filter, the battery isolator and the control panel. A 700 mm door in front of a filter that needs 900 mm of pull is a door that gets removed and never refitted, and the canopy then runs with an open aperture and a noise complaint.
What Ganesh runs for genset canopies
Canopy work starts on the 12 kW fibre laser with its 40 ft × 16 ft bed, which nests a 4,000 mm side panel and a door skin on the same sheet and cuts the louvre apertures in the same operation. Panels bend on the 200 T, 5-axis brake with a 4,450 mm bed, frames are welded in one of three CLOOS robotic MIG cells or at a manual station with a fixture made in our tool room, and the assembly goes through the 16 ft × 16 ft blast chamber where the weld scale needs it, then the seven-tank line, the 18 ft × 14 ft powder booth and the curing oven.
Canopy and base frame are made in the same plant, which is why the door alignment and the mount holes stay in one tolerance chain. Customer work in this shape includes canopy and base frame kits for Mahindra Powerol, and the part family is listed under genset parts.
The canopy hub indexes the detail articles: louvre panel design covers blade angle and free area, how a canopy frame is manufactured covers the frame and fixture route, and bending for genset canopies covers the long-panel forming. Before a quote, the canopy RFQ checklist lists the inputs that change the price.
What to put on the canopy drawing
- Set rating, site ambient and altitude, so the airflow can be checked rather than assumed.
- Acoustic target in dB(A) at 1 m, the measurement standard and the octave bands if the site has a tonal problem.
- Louvre positions and free area, marked on each elevation, with the inlet and outlet ends identified.
- Door size, swing, hinge side and latch type, plus the seal specification.
- Exhaust and cable penetration locations, with the sleeve or gland plate details.
- Coating system and corrosivity category, and the masked or bare faces.
- Lifting points and mass, because a 500 kg canopy is rigged, not carried.
- Base frame interface: mount hole pattern, pitch, diagonal tolerance and the plinth detail.
When a fabricated steel canopy is the wrong answer
A containerised or skid-mounted package that has to be shipped as a certified unit is usually built around a moulded or GRP canopy with a steel subframe, and the acoustic lining is part of the moulding. We build steel.
We also do not run the acoustic test. The canopy is measured on the set, at the OEM's test cell or by a test house, to ISO 8528-10; our evidence is dimensional, weld and coating data against the drawing. If the contract needs a sound pressure certificate with each unit, that test has to be planned into the first article rather than added at dispatch.
And a canopy for a set above about 1,000 kVA stops being a folded box. The panels get long, the doors get heavy, and the airflow needs a ducted inlet and a remote radiator. That is a different structure, and it should be quoted as one.
Send the set rating, the acoustic target and the site conditions with the drawing through the RFQ route, and the quotation will show the louvre area and the coating system it assumes.
Frequently asked questions
What is a DG set canopy made of?
A welded steel frame in 2 mm formed channel, skin panels in 1.6–2.0 mm CRCA, fixed louvre blades in 1.2 mm and doors in 1.5 mm, finished with 70–90 µm of polyester powder. Aluminium and GRP canopies exist, but steel is the default for a fabricated canopy in India.
How much noise does a DG set canopy reduce?
A well-built steel canopy with sealed doors and acoustic louvres takes 20–25 dB(A) off the bare set at 1 m. The panels themselves calculate to 30 dB and above at mid frequencies; the overall figure is set by the louvres and the leaks.
How much louvre area does a 250 kVA canopy need?
About 110–130 kW of heat leaves through the cooling air, which at a 15 K rise is 6.5–7.5 m³/s. At 3 m/s face velocity that is 2.2–2.5 m² of free area, or roughly 4 m² of louvre aperture at 55–65% free area, split between inlet and outlet.
Does a canopy derate the generator?
It can. A canopy that starves the radiator raises the intake air temperature, and a set rated at 40 °C ambient loses output for every degree above it. The canopy has to pass the radiator flow at site ambient, not at factory test conditions.
Can Ganesh build the base frame as well as the canopy?
Yes. Canopy and base frame are fabricated in the same plant, which keeps the mounting holes, the lifting points and the door alignment in one tolerance chain instead of two suppliers.
Sources and further reading
- ISO 8528-10 — Reciprocating internal combustion engine driven alternating current generators: measurement of airborne noise · reviewed 3 Nov 2026
- ISO 12944-2 — Corrosion protection of steel structures: classification of environments · reviewed 3 Nov 2026
- CPCB — Noise limits for diesel generator sets under the Environment (Protection) Rules · reviewed 3 Nov 2026